cAT Cooling Tower

Crafted from decades of engineering know-how, the Containerized (cAT) cooling towers series from EVAPCO features state-of-the-art induced draft, counterflow technology to deliver superior operating advantages in any climate. From performance to maintenance, they simply work smarter.

  • Containerized: designed to fit completely inside 20 and 40 foot shipping containers, reducing costs
  • Ranging in capacity from 174 to 459 nominal tons

evapco-at-ut-uss-cooling-tower

Warm water from the heat source is pumped to the water distribution system at the top of the tower. The water is distributed over the wet deck fill by means of large orifice EvapJet™ nozzles. Simultaneously, air is drawn in through the air inlet louvers at the base of the tower and travels upward through the wet deck fill opposite the water flow. A small portion of the water is evaporated which removes the heat from the remaining water. The warm moist air is drawn to the top of the cooling tower by the fan and discharged to the atmosphere. The cooled water drains to the basin at the bottom of the tower and is returned to the heat source. The vertical air discharge of the AT design and the distance between the discharge air and fresh air intakes reduces the chance of air recirculation, since the warm humid air is directed up and away from the unit.

EvapPak Fill
  • Constructed of inert polyvinyl chloride (PVC)
  • Resistant to rot or decay
  • Capable of water temperatures up to 130ºF
  • Usable as an internal working platform
  • Flame spread rating less then 25 per ASTM E84
High-Efficiency Drift Eliminators
  • Limits the drift rate to less than 0.001% of the recirculating water rate
  • Limit the potential of spreading Legionella
  • Constructed of an inert polyvinyl chloride (PVC)
Superior Air Inlet Louver and Screen Design
  • Constructed of an inert polyvinyl chloride (PVC)
  • Water and Sight Tight (WST) design that minimizes splash-out and the potential for algae formation inside the tower
  • Framed in steel in easily removable sections
Pressurized Water Distribution System
  • Constructed of schedule 40 polyvinyl chloride (PVC) pipe and ABS plastic nozzles
  • The piping is easily removable for cleaning
  • The nozzles are large orifice and have no moving parts, making them practically impossible to clog
Stainless Steel Cold Water Basin
  • Available in Type 304 or Type 316 Stainless Steel
  • Includes the entire basin area including the support structure, vertical columns, louver frame, and the plenum
  • Welded basin seams for leak-free operation
Stainless Steel Casing & Fan Section
  • Available in Type 304 or Type 316 Stainless Steel
  • Includes the entire upper section including mechanical equipment support, fan cowl, and fan guard
Maintenance Accessories

The cAT product line is available with multiple equipment options to aid in the maintenance of the cooling tower. These options include:

  • External Service Platform
  • Sloped Ladder
  • Motor Davit
Document Categories
Product Model filter

Drawing Types
Media name Drawing Type Drawing Format Product Model
CAT 27-618 Steel Support (Metric) Steel Support Print (.pdf) CAT 27-618
CAT 27-618 Steel Support (Metric) Steel Support Print (.pdf) CAT 27-618
CAT 27-618 Unit Certified (English) Unit Certified Print (.pdf) CAT 27-618
CAT 27-618 Unit Certified (English) Unit Certified Print (.pdf) CAT 27-618
CAT 27-618 Unit Certified (Metric) Unit Certified Print (.pdf) CAT 27-618
CAT 27-618 Unit Certified (Metric) Unit Certified Print (.pdf) CAT 27-618
CAT 27-718 CAD Drawing CAD Drawing CAD Drawing (.dwg) CAT 27-718
CAT 27-718 CAD Drawing CAD Drawing CAD Drawing (.dwg) CAT 27-718
CAT 27-718 REVIT/3D Model Revit/3D Model Revit/3D Model (.rfa) CAT 27-718
CAT 27-718 REVIT/3D Model Revit/3D Model Revit/3D Model (.rfa) CAT 27-718